ZE/WU

Sampling and Air Bleed Valve deflagration proof

Caractéristiques

Opening by Hand Wheel
Opening by Hand Wheel
Atmospheric Deflagrations
Provides Protection Against Atmospheric Deflagrations of Product Vapor/Air Mixtures
Any Installation Position
(taking the Set Pressure into Account)
End-of-line Deflagration Flame Arresters
Can Also Serve as Venting and Breathing for Tanks, Equipment Parts, and Pipelines
For Flammable Liquids
Useable for Nearly All Flammable Liquids
Robust Design
Simple and Robust Design

Fonction et description

Main Component – PROTEGO® Flame Arrester Unit

The Sampling and Air Bleed Valve PROTEGO® ZE/WU consists of the threaded angle valve in pressure Pressure (gauge pressure) Pressure for which the value is equal to the algebraic difference between the absolute pressure and the atmospheric pressure. stage PN25 (1) with hand wheel as standard design, a female threaded connection (pipe thread G½“up to G1“), and the flame arrester Flame arrester Device fitted to the opening of an enclosure, or to the connecting pipe work of a system of enclosures, and whose intended function is to allow flow but prevent the transmission of a flame. (2) with cover (3). Optionally, an elbow fitting (4) is available as outlet for sampling. The PROTEGO® Flame Arrester (2) consists of the Flame Arrester casing with FLAMEFILTER®. The valve opens manually with the hand wheel. For sampling, a suitable container is required.

For Explosion Group IIB

The simple and sturdy design makes it suitable for nearly all flammable liquids. This device Device A device is a pipe component that influences the media flow by opening, closing, or partially shutting off the flow channel or by dividing or mixing the media flow. can be installed in any position. Flame transmission protection is guaranteed against atmospheric deflagrations of gas/air mixtures or product vapor/air mixtures of explosion Explosion Abrupt oxidation or decomposition reaction producing an increase in temperature, pressure, or in both simultaneously. groups up to IIB IIB (NEC group D to C) up to an operating temperature Operating temperature Temperature reached when the equipment is operating under design conditions. of +60°C / 140°F and an absolute operating pressure Operating pressure Operating pressure is the pressure existing at normal operating conditions within the system being protected. of up to 1.1 bar / 15.9 psi. EU conformity according to the currently valid ATEX directive. Approvals according to other national/international regulations on request.

Get in Touch

Contactez nos ingénieurs

Données produit

Dimensions

DNabØ cdef
G½"40 / 1.57140 / 5.5170 / 2.7680 / 3.1596 / 3.7867 / 2.64
G¾"50 / 1.97165 / 6.5085 / 3.3580 / 3.1589 / 3.5067 / 2.64
G1"65 / 2.56200 / 7.87100 / 3.9495 / 3.74104 / 4.0967 / 2.64

Dimensions in mm / inches

Material

DesignA
Threaded angle valveStainless Steel
ElbowStainless Steel
CoverStainless Steel
FLAMEFILTER®Stainless Steel

The valves must be sufficiently resistant to corrosion through the gas/air mixtures or product vapour/air mixtures. This applies mailnly to the FLAMEFILTER®.

Explosion group

MESGExpl. Gr. (IEC / CEN)Gas Group (NEC)
≥ 0,50 mmIIBB

Type of connection

Pipe thread DIN ISO 228 T1DIN

Design Types and Specifications

There are two designs available:
Sampling and air bleed valve, standard designZE/WU - 1
Sampling and air bleed valve with elbowZE/WU - 2
Special designs for higher pressures are available

Optionally available with fl ange connection (see fi gure)

* position of drilling holes on flange connection as well as thickness upon request for size DN 15 / ½", DN 20 / ¾", DN 25 / 1", DN 32 / 1¼", DN 40 / 1½" and pressure nominal PN 25/40 resp. PN 100 available